2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Cl at 0.5 ppm. Operator turned up chlorinator but was unable to increase chlorine levels. .2535(4) Maintain chlorine at least 1.0 ppm. - Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Cyanuric Acid at 100 ppm for the last month in pool log book. Tested today at 0ppm. .2535(3) Outdoor pools that use chlorine must be stabilized with cyanuric acid not to exceed 100ppm. - Intent to suspend item.
PH 7.8. Every day for the month of July. .2535 (11) The pool operator shall inspect the pool at least daily and maintain written records using a test kit to check water chemistry. - Intent to suspend item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Missing 2 of 5 weirs. .2518(k) Replace missing weirs. - Intent to suspend item.
Skimmer basket broken, pieces floating in skimmer. .2518(k) Replace missing or damaged skimmer basket. - Intent to suspend item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Two of three gates not self-closing and self-latching. .2528(a) Access gates shall swing away from the pool and be self-latching, self-closing. - Intent to suspend item. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Hole in the deck where one deck drain cover came off. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Ensure chlorinator is working properly. No flow on flow meter for erosion feeder observed. Low salt warning light on salt cell observed. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Bad leak at filter, water running away from pump room drains and under the pump room wall. .2533(d) Pump room floor shall be kept dry and free of standing water.
Boxes of chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |