| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Two chlorine tabs in the skimmer closest to the pump room. G.S. 130A-2(3) Chlorine added directly to swimming pool. Chlorination must occur through chlorinator. Eliminate direct hazard to public. - Pre-permit item. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
PH 8.2. .2535(1) Maintain pH at 7.2 to 7.8. - Pre-permit item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No recent Total Alkalinity readings. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, and pool water maintenance. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Pre-permit item. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pool floor dirty, some algae growing in the corners on the sunshelf. .2537(14) Keep pool surface and pool floor free of debris. - pre-permit item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Missing one weir. .2518(k) Replace missing weirs. - Pre-permit item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder loose. .2521 Install ladders per manufacturer instructions. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Most of the fencing < 48" due to layers of pine straw. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. - Pre-permit item. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
Some safety signage missing. .2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. - Pre-permit item.
Some safety signage missing. .2530(c) Provide "Adults should not swim alone." in 1" lettering. - Pre-permit item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Digital flow meter not functioning. .2518(g) Keep flow meter operational. - Corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan in chemical storage room not functioning. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
A few different leaks in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
Some chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |