Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameSTONE RIDGE APTS - LARGE POOL
Address8940 CAMDEN CREEK LN
 
City/State/ZIP
CHARLOTTE NC 28273
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 7/8/2026
Final Score @ Grade
32
General CommentsInspection conducted with CPO, Sheronda Howard. Permit issued. Not approved for night swimming. All critical violations corrected during inspection. Permit restrictions: Flow meter must remain operable. Flow required at 107gpm-141gpm to meet turnover and filter flow restriction or pump shall be set to 3450RPM. Field verification conducted.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No .2535(4) Maintain chlorine at least 1.0 ppm through NSF approved chlorinator. Observed chlorine at 0.5ppm. Corrected- Chlorine increased to 1.5ppm with stick feed chlorination.
3 6 Water quality: pool water pH No No No .2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.8. Corrected- CPO adds soda ash and increases pH to 7.8
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No .2537(14) Keep pool surface and pool floor free of debris. Observed substantial leaf litter in pool. Main drains and suction outlets still visible. Corrected- pool being vacuumed during inspection.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmers full of leaf litter. EHS advised CPO to clear baskets.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No .2537(b) All gates and doors shall be self-closing, self-latching. Observed one side gate not self latching. Corrected- CPO padlock and chains gate. Gate also monitored during all hours of operation by attendant in leasing office. CPO intended to begin permanent repair this week and will follow up with EHS when complete. Repair gate so it is self closing and latching by 08/08/2026.
22 6 Premises: emergency telephone provided No No No .2530 Emergency phone shall either audibly ring or answer automatically when phone number for phone is dialed. Observed incorrect phone number listed for incoming calls at Kings 3 box. Corrected- Accurate phone number label made and added at sign above box.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No .2534(4) Provide provisions for dry storage in waterproof containers or above the floor on shelves, pallets or dollies. Observed bagged chemicals on floor in chemical room. Provide rack to store chemicals off ground.