General CommentsPermit Restriction: Flow meter must remain operable. Flow required at 107 gpm to 141 gpm to meet turnover and flow restriction of the filter - or - pump shall be kept at 3450 RPM. All the following was verified during inspection: New Pump Pentair Intelliflo VSF 011056, 3.95 Blue white flow meter reading in the above range. Main drain, skimmer and return line all 3” line coming out of the pump room floor. (2) Paramount SDX2 drain covers 2008 (4) skimmers with (4) Aquastar 2008 A10RCFRxxx EQ line covers. (1) Pentair TR140C filter (8) returns either on the wall or the floor.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No .2535(4) Maintain chlorine at least 1.0 ppm. Observed chlorine at 0.4. -CDI- CPO corrected to 4.0.
3 6 Water quality: pool water pH No No No .2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 8.0. -CDI- CPO corrected to 7.2.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No .2537(14) Keep pool surface and pool floor free of debris. Observed minor debris on pool floor.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No .2537(b) All gates and doors shall be self-closing, self-latching. Observed pool gate not self-closing, self-latching. -CDI- CPO corrected. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed door opening onto pool deck not self-closing, self-latching. -CDI- CPO corrected.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No .2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed less than 6ft clearance around pool deck. -CDI- CPO corrected. .2537(2) Decks shall be kept in good repair. Observed minor cracking on pool deck. Does not present hazard at time of inspection.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No .2518(e) Provide a spare basket for pump. Observed no spare pump basket. Per CPO, property manager has purchased it and is en route with it.