5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Main drain checks missing from records. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain
cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total
alkalinity weekly. Operator added main drain checks. Corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. Pool built '00. .2533(2) Pools constructed after April 1, 2004 shall provide a separate room for
chemical storage meeting Rule.2534.
No backflow prevention on hose bib in equipment room. .2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash. .2513(b) Filter backwash shall be discharged through an air gap. |