Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameEASTWAY REGIONAL REC CENTER - LEISURE POOL
Address3150 EASTWAY PARK DR
 
City/State/ZIP
CHARLOTTE NC 28205
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 12/18/2020
Final Score @ Grade
10
General CommentsOnsite visit to pool with Daniel Osucha for return construction and permit inspection. Construction final passed. Pool is not slated to open to the public until after January 1 and was currently not open to the public. 911 listed address at emergency phone was incorrect address. GIS mapping is currently in process of assigning a different address of 3150 Eastway Park Dr. Signage made to match 911 address of 423 Eastway Dr. Once address is changed with phone company and 911, signage must match. Given 30 days to correct phone address to 3150 Eastway Park Dr or permit will be suspended. Address point in polaris currently; however, when entered into gps 423 Eastway will get you to property. General Comment - Slide flow meter at 550 gpm. Mfg. recommendations at 600 - 800 ppm. Facility added barrier around slide that does not maintain 5 ft. clearance from the edge of the pool. Due to safety hazard of protrusions on slide and phone conversation with Stacie Rhea, Regional, determined that safety of public permitted the barrier. Plan review approved distance on back side of slide to wall at 4 ft. Permit Restrictions 1) Feature pump (PP5) flow meter must remain operational not to exceed 218 gpm due to feature pipe restrictions. 2) Waterslide flow meter must remain operational (located on waterslide). Range at 600 – 800 gpm per mfg. requirements. 3) Digital flow meter must remain operational on backwash line. Backwash flow shall not exceed 394 gpm. Lock valve in place. 4) Portable vacuum required for vacuuming of pool.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Records not maintained on weekends. Pool is not open to the public yet. Ensure daily record keeping when pool is open.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Some weirs sticking. Continue to monitor and repair if worsens so skimmers remain operational.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Soap not provided at every sink. No toilet paper in stalls. Two toilets in women's requiring cleaning. Provide soap and toilet paper in restrooms and ensure all fixtures are clean.