24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Permit condition for functional flow meter on backwash line to verify backwash per manufacturer’s instructions. Flow meter not functioning, clogged with lint and debris. .2519(d) Sand filters shall be designed and installed to be backwashed per manufacturer’s instructions, that is between 356 GPM - 474 GPM. Corrected - flow meter cleaned, verified at ~ 390 GPM. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan not working in either of the chemical storage rooms. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage rooms. |