3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8.
Observed pH measuring 6.9 - 7.0 (readings from both EHS and CPO's test kits).
CDI CPO added more soda ash into pool while EHS still on-site. EHS observed pH was now reading 7.2. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
Observed minor debris in skimmers.
CDI CPO dumped out skimmers. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
Observed callback number was different from number provided by dispatch operator. Observed a torn piece of paper was covering callback number.
CDI signage posted with correct callback number of 912-740-8811. |