Water quality: pool water pH |
No |
No
|
No |
Pool pH at 6.8. Added chemicals during inspection but no change. Appears to be issue with automated feeder. Maintain pool pH at 7.2 to 7.8. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No records for cyanuric acid or total alkalinity. Maintain weekly record keeping for cyanuric acid and total alkalinity.
Test kit tube with black dot worn off for cyanuric acid test. Replace test kit. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Debris on pool floor and on sun shelf. Keep pool floor clean and in good repair. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Debris under skimmer baskets on multiple skimmers. Keep free of debris so functioning correctly. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Signage missing from emergency phone. Provide correct address and phone number at phone. Address is 101 W Morehead St. Phone number of 980-949-8537. Verified callback at time of inspection. Immediate Suspension issued.
Pool rules signage with dialing instructions and incorrect address located across pool. Correct address on pool rules sign. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Automatic feeder for chlorine and pH not detecting flow and continuously running. Repair so that feeders detect flow and shut off when no flow from pump. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Dry chemicals stored in pump room on floor and not in chemical storage room. Keep chemicals stored in chemical storage room as not to present a hazard. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms at 112 F. Maintain at 110 F or below. |