| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Non-slip tread missing from one of the ladders. .2521 Install ladders per manufacturer instructions. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Skimmer equalizer lines plastered over, but not plugged in the skimmer. Ensure skimmers are abandoned per state guidelines. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Intent to suspend item. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Throw rope 47 feet long. .2530(a) Provide USCG approved ring buoy with 45 foot long throw rope at least 1/4" in diameter. - Intent to suspend item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door to clubhouse does not latch, not alarmed. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. - Intent to suspend item. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some deck chairs too close to pool edge or ladder. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck.
.2522(a) Provide 6 ft of clear walking space around the pool at all times. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Underwater light not secured to the pool wall. .2537(9) Underwater light niches shall be maintained or covered so not to present a hazard. - Intent to suspend item. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone not functioning. .2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system. - Immediate suspension item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Eyeball fitting installed on vacuum line closest to the pump room. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. Corrected by operator. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan not functioning in the pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Fan not functioning in the chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Lighting not functioning in the chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Newly installed piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in the restroom > 110F. .2526(i) Water in restrooms shall not exceed 110 F. |