Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameAVALON SOUTH END
Address2250 HAWKINS ST
 
City/State/ZIP
CHARLOTTE NC 28203
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 4/1/2026
Final Score @ Grade
22
General CommentsIntent to Suspend issued for: .2518 - repair flow meter so operable. .2537 - repair hole at coping. .2525 - repair automated feeder - shall detect flow with loss of power. Lance Wolfe present during the inspection. Note: Main drains expire in 2030 and will need to be replaced prior to expiration. 2017 Lawson drain covers require specific installation instructions. Ensure new drain covers are compatible with sumps and also maximum capacity of the drain covers.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Some debris on pool floor, on drain covers. Keep drain covers free of debris.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Skimmer baskets full of leaf debris. Keep clean to ensure skimmers operating as required by NSF.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Pool lounge chairs within 5 ft. of pool edge. Maintain 6 ft. clearance around pool in all locations. Damage to coping, hole greater than 1/2", at sun shelf left side step entry. Repair. Intent to Suspend issued.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No Automated feeder not detecting flow, intermittent. Tried three times and only detected flow once. Automated feeder shall detect flow from pump and turn off with loss of flow from pump. Intent to Suspend issued.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter not operable. Keep operable. Intent to Suspend issued.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Door to restroom locked. Restroom shall be kept accessible at all times. Leak at the sink. Repair leak. Facility has a bathroom indoors that can be used.