3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Pool pH at 6.8. Maintain at 7.2 to 7.8. Corrected to 7.4 during the inspection. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records not maintained for February. Missing Total Alkalinity readings for January. Maintain daily record keeping for chlorine, pH and main drain checks. Maintain total alkalinity and cyanuric acid (if used) weekly. Intent to Suspend issued. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmer baskets full of leaves and debris, including under baskets. Keep baskets free of debris so that filtration system can function per mfg. instructions. Emptied during the inspection. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Light niche missing fitting. Replace fitting around light. Intent to Suspend issued.
Bubbler return missing flush fitting. Replace. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Some damage to wood on outside of gate that enters into the parking area. Monitor. Does not warrant repair at time of inspection as wood was still in place. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pool furniture (lounge chairs) <6 ft. to pool edge. Maintain 6 ft. clearance around the pool in all locations.
Autofill offset and not flush with deck. Offset is not greater than 1/2". Monitor. Will require repair if offset exceeds 1/2".
Some damage to caulk between deck and coping near corner at autofill. Repair. Intent to Suspend issued. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Small leak at chlorinator. Repair leak. Intent to Suspend issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Floor in the pump room wet due to leak from chlorinator. Keep dry.
Fan not operable in pump room. Provide continuous forced ventilation. |