Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameAVALON AT PALISADES
Address15906 WHITE ST
 
City/State/ZIP
CHARLOTTE NC 28278
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 7/22/2025
Final Score @ Grade
20
General CommentsIssued 30 Day Intent to Suspend (ITS) for gates and overflow fitting. Contact Marie Daley at 704-507-6806 to lift ITS when items are in compliance or permit will be suspended. Property management is changing effective 8/8/2025. CPO, Tim Pietrantonio, will no longer be maintaining pool. On 8/9, advised if pool is not being checked or maintained it should be voluntarily closed until CPO is on property for adequate pool maintenance and operation. At return visit, Certified Pool Operator (CPO) must be provided with updated information on property management or permit action will be taken. “W” ITS status

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No pH 7.0 at time of inspection. .2535(1) Maintain pH at 7.2 to 7.8. Operator corrected to 7.2.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Debris in skimmers at time of inspection. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator emptied and corrected.
12 4 Pool maintenance: inlets and other fittings in place and in good repair No No No Overflow grate broken. Autofill fitting not in wall. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Operator replaced fitting and corrected. Overflow grate permit item.*
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No One gate locked by cable, gate broken. .2537(b) All gates and doors shall be self-closing, self-latching. *Permit item