15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Observed ring buoy not USCG approved.
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Observed damaged section of deck at coping near underwater bench toward pump room.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
Observed signage for lifeguard on duty and warning sign too small, 1” and 1/2” letters respectively.
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering.
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering.
.2530(c) Provide "Adults should not swim alone." in 1" lettering. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Observed flow meter not properly installed.
.2518(g) Install flow meter on return line per manufacturer instructions. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Observed no air gap on backwash line.
.2513(b) Filter backwash shall be discharged through an air gap. |