5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
Observed no section/column in log book for recording total alkalinity or cyanuric acid. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Observed ring buoy with rope length of 45ft (based on pool square footage rope must be 46.6ft). |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
Observed doors with direct access to pool deck inaccessible- residents not notified/not at residence during inspection. Fencing around perimeter of pool not to code. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times.
Observed cabanas next to pool with less than 6ft clear walking space.
.2522(f) Deck shall be sloped to drain.
Observed no drains on pool deck.
PERMIT CAN BE ISSUED FOR 2024 SEASON; HOWEVER PRIOR TO 2025 SEASON POOL DECK MUST BE SLOPED TO DRAIN/REPAIRED. IN-FIELD PLAN REVIEW REQUIRED. CONTACT TIM DUCTHER (704-507-6808) OR KATIE RUDISILL (704-309-5494). |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Emergency phone shall remain operable.
Observed emergency phone unable to be called back. EHS able to dial out to 911 (phone # and address on file with 911 is correct). |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational.
Observed flow meter inoperable. PIC able to make flow meter operate but meter gets stuck easily. |