7
|
0
|
Facilities provided, accessible, clean, good repair |
No |
No
|
No |
General Comment:
.1312 (a) All institutions shall provide toilet, handwashing, and bathing facilities that are available for use by residents and staff. These facilities shall be kept clean and in good repair.- Observed slow drain in Charlotte room 302 need repair. Ceiling vent in the Asheville Spa room and Charlotte Laundry room need cleaning. Restroom baseboard wall in Charlotte room 308 needs repair. |
|
8
|
0.50
|
Toilet rooms free of storage, handwash signs posted |
No |
No
|
No |
.1312 (b) A sign shall be posted in each toilet room for institution employees, directing them to wash their hands after each visit to the toilet room and before returning to work.- Observed no hand washing sign in restroom hallway and half of the facility restrooms. Ensure to post hand washing signs in all restrooms. |
|
10
|
0
|
Handwashing facilities properly located and equipped |
No |
No
|
No |
General Comment:
.1312 (d) Handwashing facilities shall be supplied with soap and disposable towels or hand-drying devices.
- Observed no soap and or paper towels in Charlotte room 302, Charlotte spa room and soiled utility room. Ensure to provide all hand washing supplies at all hand sinks at all times. |
|
16
|
1.50
|
Hot water between 105°F and 116°F |
No |
No
|
No |
REPEAT
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities.
- Observed hot water temperature measure at 119F in rooms 205, 214 in Asheville, 121F in the Charlotte spa, 123F in Wilmington room 411, 404, common area sink at 121F. Ice cream shop at 92F, common area sink in Asheville and Charlotte at 87F. Ensure to provide tempered water evenly throughout the facility at anytime. Point remain the same at this times. |