2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
G.S. 130A-2(3) Chlorine added directly to swimming pool. Chlorination must occur through chlorinator. Eliminate direct hazard to public. Observed chlorine pucks in skimmer baskets. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. Observed reagents expired in 2022 & 2023. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Observed 2 missing weirs. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism. Observed mesh in need of repair near gate latch due to openings greater than 1/2”. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2537(2) Decks shall be kept in good repair. Observed minor cracking in deck. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. Observed damaged flow meter.
.2518(e) Provide a spare basket for pump. Observed no spare pump basket. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Observed cyanuric acid stored on floor in chemical storage room. |