Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameMALLARD GLEN APARTMENTS
Address2002 LAYSAN TEAL LN
 
City/State/ZIP
CHARLOTTE NC 28262
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 12/12/2022
Final Score @ Grade
20
General CommentsIssued intent to suspend for missing records and inoperable flow meter. Return visit to take place in 30 days. Please call James Bjorneboe with any questions at 704-507-6820.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Observed no records for December. Keep daily records while pool is in operation. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Observed 1 of 4 weirs missing. Replace. .2518(k) Replace missing weirs.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Both ladders missing end caps. Replace missing end caps.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No Observed throw rope at 52 feet. Throw rope must be 50 feet. Corrected on site.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Observed in operational flow meter. Repair. .2518(g) Flow meter be capable of measuring 1.5 times the design flow rate.