| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
No free chlorine in the pool. .2535(4) Maintain chlorine at least 1.0 ppm. - Immediate suspension item. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
pH > 8.4. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No records since February. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Intent to suspend item. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Vacuum cap open, vacuum line on. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. - Immediate suspension item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One weir stuck in the skimmer, not functioning properly. .2518(k) Install functional weirs. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Body hook missing a screw. .2530(a) Provide at least 12 ft. long pole with body hook securely attached. - Immediate suspension item. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
Warning No Lifeguard on Duty signage in less than 4” lettering. .2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. - Intent to suspend item. |
|
19
|
4
|
Premises: signs prohibit glass containers or pets in pool area |
No |
No
|
No |
Safety signage not visible from all pool entrances. .2530(d) Provide a sign prohibiting pets in the pool area. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Chlorinator not working. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Intent to suspend item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not working. .2518(g) Keep flow meter operational. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Some chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Standing water on pump room floor. .2533(d) Pump room floor shall be kept dry and free of standing water.
Lots of general storage in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
One stall in women’s restroom with broken toilet paper holder. .2526(l) Provide toilet paper and dispensers in restrooms. |