2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Observed chlorine at .4 raised to .8 during inspection. Immediate suspension issued.
.2535(4) Maintain chlorine at least 1.0 ppm. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Observed no checks for main drains and total alkalinity.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Observed flow meter dirty, not able to be read and not properly installed
.2518(g) Keep flow meter operational. Install per manufacturer instructions. |