Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8.
Observed pH at 7.0
CPO unable to repair at time of inspection.
*Immediate Suspension Item |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism.
Observed distance of 0.9 inch within 18 inches of push bar on entry way closest to the main door of leasing office.
Repair or replace so that no greater than 0.5 inches.
*Intent to Suspend |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
Emergency phone sign provided incorrect dialing instructions. -CDI- Incorrect directions were taped over until new sign can be placed.
-CDI- |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(e) Provide a spare basket for pump.
Observed no spare pump basket present.
Ensure a spare pump basket is provided
*Intent to Suspend |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Observed filter on air ventilation in pump and chemical room. Filters prevented proper ventilation.
Repair or replace.
.2534(6) Provide sufficient lighting in chemical storage room.
Observed no working lighting in the chemical storage room.
Repair or Replace
.2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator.
Observed non-locked pump room.
Ensure locked when not in use. |