Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope 60ft. Operator cut to approved 45ft. Corrected. No permit action. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(e) Provide a spare basket for pump. Spare pump basket missing. Operator provided one by end of inspection. Corrected. No permit action. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. Unable to identify any backflow prevention device on any hose bibs around pool. No 3' clearance around piping and equipment. Water on floor in pump room. Pool built '90.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump
.2533(d) Pump room floor shall be kept dry and free of standing water. |