Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameAVENUES AT STEELE CREEK
Address13001 YORKRIDGE DR
 
City/State/ZIP
CHARLOTTE NC 28273
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 6/20/2025
Final Score @ Grade
36
General CommentsPool does not have a permit. Conducted inspection with CPO Joe and GM Derrick Banks. Pool not able to open due to various deficiencies. EHS Devon Moeller went through each deficiency with the responsible parties. All immediate suspension items and intent to suspend items must be corrected and reinspected prior to permit issuance and pool opening. Pump grounding wire must pass electrical inspection. Call EHS Devon Moeller when items are corrected and ready to reopen. 7049981122

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No .2535(4) Maintain chlorine at least 1.0 ppm. Chlorine observe at 0. Possible problem with automatic chlorinator. Repair. Immediate suspension item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Water level shall be maintained to assure skimmers are operable. Water level too low for skimmers to be operable. Fill. Intent to suspend item.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No .2530(a) Provide USCG approved ring buoy. .2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy and rope missing. 45’ rope required. Immediate suspension item.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Ground level door alarm not functional. Repair. Pool gate shall not have any footholds. Install slanted piece of metal above the existing footholds. Intent to suspend items.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No .2537(2) Decks shall be kept in good repair. Coping crumbling by skimmer by clubhouse. Repair. Intent to suspend item.
22 6 Premises: emergency telephone provided No No No .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Phone callback number posted not correct. 911 operator confirmed correct phone number 828-718-1876 and EHS verified call back. Post correct number. Immediate suspension item.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No .2518(g) Keep flow meter operational. EHS observed flow meter not functioning. Intent to suspend item. .2518(e) Provide a spare basket for pump. Spare pump basket missing. Replace. Intent to suspend item. .2518(h) Provide approved pump in good repair. Pump grounding wire not attached. MUST repair via an electrician and pass electrical inspection. No pump tag on pump. Provide documentation on pump to EHS.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Chemicals stored in pump room. Unable to identify any backflow prevention device on any hose bibs around pool. No 3' clearance around piping and equipment. Insulation on ground in pump room from fallen ceiling. Pool built '90. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump