Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameAVENUES AT STEELE CREEK
Address13001 YORKRIDGE DR
 
City/State/ZIP
CHARLOTTE NC 28273
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 4/8/2024
Final Score @ Grade
16
General CommentsInspection conducted with CPO Tony Jones. Intent to suspend issued for two gates that are not self latching. Call EHS Devon Moeller when repaired 7049981122.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No .2535(1) Maintain pH at 7.2 to 7.8. Pool Ph at 6.8. Operator corrected to 7.2. No permit action.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Sporadic record keeping through the winter. Pool has been closed daily. Ensure closures are documented on records and maintain daily records moving forward when pool is open. No permit action
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No .2537(b) All gates and doors shall be self-closing, self-latching. Both front gates not self latching. Intent to suspend item. Gaps under fencing around landsecaped areas greater than 4". Pool built '90. .2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010).
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Chemicals stored in pump room. Unable to identify any backflow prevention device on any hose bibs around pool. No 3' clearance around piping and equipment. Water on ground in pump room. Pool built '90. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump .2533(d) Pump room floor shall be kept dry and free of standing water.