Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Pool Ph at 7.0. Corrected to 7.2 during inspection. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions. Ladder loose. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Lifesaving equipment should be conveniently located. Ring buoy with heavily tangled rope such that is not usable. Operator corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gaps under fencing around landsecaped areas greater than 4". Pool built '90. .2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Two phone numbers posted at Kings III emergency phone box - neither is accurate. 911 operator confirmed correct phone number 980-226-5838 and EHS verified call back. Operator corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. Unable to identify any backflow prevention device on any hose bibs around pool. No 3' clearance around piping and equipment. Water on ground in pump room. Pool built '90.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump
.2533(d) Pump room floor shall be kept dry and free of standing water. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
.2518(d) Piping and valves shall be labeled with color codes or labels. Unable to identify labeling on most pipework in pump room. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
.2526(h) Shower(s) shall be provided. Shower broken. |