Premises Information

Return to Inspections
NameCHARLOTTE MARRIOTT SOUTHPARK
Address2200 REXFORD RD
 
City/State/ZIP
CHARLOTTE NC 28211
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 10/28/2019
Final Score @ Grade
38
General Comments15 - Grab rope on ring buoy starting to degrade. Replace with USCG approved ring buoy with 35 ft. rope by November 1. A return visit will be made on Friday to verify replacement or permit will be suspended. Current rope length is too short but what was listed in book at 30 ft. Provide at 35 ft. 22 - Per 911 operator, inspector not clearly audible. Recommend having phone looked at to ensure emergencies are clearly audible from emergency phone. Intent to Suspend issued for CYA record keeping, replacing weirs, repairing doors to self-close, self-latch or audible alarm, Warning signage, and pool light.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No Pool pH at 8.4 upon arrival. Lowered to 7.4 during inspection.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Cyanuric acid not recorded weekly. Record weekly. Intent to Suspend issued.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No All skimmers missing weirs. Replace skimmer weirs. Intent to Suspend issued.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Ladder rungs >6" from pool wall. Maintain 3" to 6" between pool wall and rungs.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Doors on to pool deck from fitness self, close but do not self-latch. Repair doors to self-close with audible alarm. Glass could not be verified as tempered along with other glass items in fitness room. Fitness room not approved as part of pool deck. Intent to Suspend issued for doors. One door dog-earred back to self, close but not self-latch. Corrected during inspection. Furniture and railing outside of pool barrier provide footholds. Eliminate footholds.
18 4 Premises: lifeguards present or warning signs posted No No No Warning signage too small. Intent to Suspend issued. .2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering.
21 4 Premises: pool and deck lighting provided at pools that operate at night No No No Light burnt out in pool. Pool approved for night swimming. Repair light. Intent to Suspend issued.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No Pool only utilizing salt. Pool not approved for salt as primary chlorination. Required to use stick feeder as primary chlorination.
26 2 Equipment room: valves and pipes identified by color codes or labels No No No Valves and piping not clearly identifiable in pump room. Clearly identify all pipes with color codes and/or labeling.
30 2 Dressing and sanitary facilities: approved water source, no cross connections No No No Fill line check valve ASSE 1015 rated. If ever replaced, replace with approved check valve. .2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer.
33 2 Dressing and sanitary facilities: hose bibbs and floor drains provided No No No No hose bib or floor drain in pool restroom in fitness room. No hose bib in pool pump room. Provide hose bibs with backflow prevention device and floor drains as needed.