3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.0. Permit suspended. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed pool data not being recorded daily. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
.2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. Observed one area of pool where depth markers on pool wall are spaced greater than 25 feet apart.
.2523(c) Depth markers shall include the word "feet" or symbol "ft". Observed one depth marker on the pool wall that does not have "ft" or "feet." |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed one damaged overflow grate missing vertical slats. Observed one return fitting on pool floor damaged. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Observed some areas around fence with area underneath in excess of 6" clearance.
.2537(b) All gates and doors shall be self-closing, self-latching. Observed door from front office that leads onto pool deck not self latching. Observed gate that leads directly onto pool deck not self latching.
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Observed windows in weight lifting room that lead directly onto pool deck that open greater than 4 inches.
.2528 Eliminate footholds around fencing. Observed foothold on gazebo fencing next to pool fencing at 42" high.
.2537(b) All gates and doors shall be self-closing, self-latching. Observed maintenance gate chained shut. Permanently affix gate so it is no longer operational. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Emergency phone shall remain operable. Observed emergency phone non-operational. Permit suspended. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Observed air break for filter backwashing; no air gap. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
.2512(a) Water supply serving the swimming pool and all plumbing fixtures shall be an approved water supply. Observed no check valve installed on water fill line in pump room. |