2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(4) Maintain chlorine at least 1.0 ppm. Chlorine was at 0.4ppm upon arrival. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH out of safe range. It was corrected to 7.6. -C.D.I. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
.2535 (4) Lower and maintain cyanuric acid at or below 100 ppm.
Observed gaps in the log recored. No permit action taken. Keep the records properly. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Observed 1 missing weir. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed 1 missing eyeball fitting. Replace the fitting. No permit action taken. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Emergency phone shall remain operable. Emergency phone failed during the inspection due to community wide lost of tel-com utility service during the inspection. C. Elmore will follow-up on 4/16/2026. Immediate Suspension issued. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. Observed chlorination system not on-line upon arrival. System was brought on-line during the inspection. -CDI. Disinfectant must be maintained through the disinfectant system. It cannot be manually fed into the water for normal operation. It may only be manually fed for shocking or maintenance operations when the pool is kept closed until normal operation with the disinfectant feeder system is resumed. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. Observed flow meter to be stuck. Correct flow meter. No permit action taken. |