Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
Drain covers installed in pool do not match main drains listed on PDSC. CPO indicates that Aquastar 12MF101 drain covers were replaced in 2021 - Most recent PDSC is from 2019. Updated PDSC form shall be completed and evaluated before permit can be issued. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs.
Observed one of 4 weirs missing from skimmers. Corrected - CPO replaced cover during inspection.
.2518(k) Replace missing or damaged skimmer basket.
Minor damage to a couple skimmer baskets. Not in need of immediate replacement. Replace as needed. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Ring buoy rope observed >50ft. Corrected - CPO cut rope to 50ft. |