5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No recent main drain checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity. - Intent to suspend item. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
One of the WAV12WR main drain covers damaged. .2537(7) Drain covers shall be in good condition and securely attached. - Immediate suspension item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
1 of 6 weirs missing. .2518(k) Provide functional weirs. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Top of bubbler missing on sunshelf. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Outer rope on ring buoy and throw rope heavily frayed. .2530(a) Provide USCG approved ring buoy with attached 50 foot throw rope at least 1/4 inch in diameter. - Immediate suspension item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Spare pump basket for filtration pump not observed. .2518(e) Provide a spare basket for pump. - Intent to suspend item.
Flow meter not working. .2518(g) Keep flow meter operational. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Fan not working in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Some of the labeling on pool equipment piping worn off. .2518(d) Piping and valves shall be labeled with color codes or labels. |