2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(4) Maintain chlorine at least 1.0 ppm. Chlorine measured 0.0 ppm. Upon inspection, found chlorinator has not been installed. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Debris in skimmers |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Erosion of soil under fence near pump house (due to recent torrential rains) resulted in clearance exceeding 12” in some areas. Restore stable substrate under fence to achieve required clearance under fence. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Posted phone number is incorrect. Provide notice for correct number. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. No automatic chlorinator has been installed. |