8
|
0
|
Toilet rooms free of storage, handwash signs posted |
No |
No
|
No |
.1312 (b) A sign shall be posted in each toilet room for institution employees, directing them to wash their hands after each visit to the toilet room and before returning to work. Observed no handwashing signs in Pine Building 3rd and 4th floors, Palmetto Tower 7th floor and staff lounge on 2nd floor. |
|
16
|
0
|
Hot water between 105°F and 116°F |
No |
No
|
No |
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. Observed hot water in Endoscopy procedure room 1 reach 93F and Radiology department between 70-93F. Ensure hot water is between 105F-116F. |
|
38
|
1
|
Food service equipment and utensils clean, good repair |
No |
No
|
No |
.1320 (a) All food service equipment and utensils shall be kept clean and in good repair. Observed nourishment room refrigerators on 2 West and in ICU in need of cleaning. Observed nourishment room microwave in Pine Building 4th floor in need of cleaning. REPEAT |