2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
OBSERVED CHLORINE TO BE 0.1PPM OR LESS IN THE POOL. 1.0PPM IS REQUIRED MINIMUM FOR A POOL. OBSERVED DISINFECTANT FEEDER SYSTEM TO BE CURRENTLY NON-FUNCTIONAL. I.S. ISSUED AND POOL WAS CLOSED TO SWIMMING BY THE HEALTH DEPARTMENT. DISINFECTANT CANNOT BE HAND FED FOR NORMAL OPERATION, IT MUST BE FED INTO THE POOL THROUGH THE DISINFECTANT SYSTEM FOR NORMAL OPERATION WITH THE POOL OPEN FOR SWIMMING. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
OBSERVED 1 WEIR MISSING OUT OF 3 SKIMMERS TOTAL. NO PERMIT ACTION TAKEN. REPLACE THE WIER. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
OBSERVED A GAP IN THE FENCE DUE TO DAMAGE. REPAIR THE FENCE. FENCE WAS CONSTRUCTED PRIOR TO APRIL 2010. NO PERMIT ACTION TAKEN. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
OBSERVED THE POOL PUMP TO HAVE THE GROUND WIRE DISCONNECTED FROM THE PUMP. WIRE COULD NOT BE CONNECTED BY STAFF MEMBER DURING INSPECTION. IF THIS PUMP WAS CHANGED WITHOUT PROPER ELECTRICAL INSPECTION OR PERMITS, THE ISSUED MAY HAVE TO BE RESOLVED WITH THE PROPER CODE ENFORCEMENT DEPARTMENT. THE PUMP WAS ALSO DAMAGED AS THE CAPACITOR WAS DISLODGED FROM THE HOUSING AND ONE OF THE WIRES WAS DISCONNECTED. THE DISCONNECTED GROUNDING WIRE MAY PRESENT AN ELECTRICAL HAZARD. I.S. ISSUED. REPAIR THE PUMP. IF THE PUMP IS REPLACED NOTIFY THE HEALTH DEPARTMENT AS A NEW P.D.S.C. FORM MAY BE REQUIRED. |