Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameBRIDGES AT MALLARD CREEK
Address7916 HARRIS HILL LN
 
City/State/ZIP
CHARLOTTE NC 28269
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 5/30/2024
Final Score @ Grade
18
General CommentsInspection conducted with CPO Randy. New Pentair SuperflowVST pump installed. Electrical permit E4595394 passed inspection 3/25/2024. New permit condition. Flow meter must remain operable and read between 59 GPM and 63 GPM to meet minimum turnover and flow restriction of the filter. Deck chipping around handrail. Maintain in good condition. Main drains expire 9-26-2025. Replace with ANSI/APSP/ICC-16 approved drain covers and provide updated Pool Drain Suction Compliance form to MeckPools@MeckNC.gov for approval. Contrasting color bands fading. Prior to 2025 permit being issued. Will need to repaint at least 2” wide contrasting color band at leading edge of pool steps. Takes a while for Kings III to connect when calling back to the box. Recommend to have Kings III adjust to connect in 3 rings or less. Permit issued. Paper permit will be issued online in 3-5 days for your records.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No PH 7.1. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.2.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Ladders extend > 6" into the pool. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. Ladders missing endcaps. .2521 Install ladders per manufacturer instructions. - Corrected.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Fan not working in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
26 2 Equipment room: valves and pipes identified by color codes or labels No No No Some piping labels faded. New piping for new pump not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
27 2 Equipment room: filter backwash discharged through an air gap No No No No air gap for backwash line. .2513(b) Filter backwash shall be discharged through an air gap.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No One faucet in men’s restroom and one faucet in women’s restroom not functioning. .2526(m) Keep restrooms and fixtures clean and in good repair. New mirrors. Not able to determine if shatterproof or have safety backing. .2526(k) Provide shatterproof mirrors.
33 2 Dressing and sanitary facilities: hose bibbs and floor drains provided No No No Hose Bibb for restrooms not observed. .2526(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose.