Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
New Pentair WhisperfloXF pump installed in July 2019. Pump, model XFE-20 has a max flow of 290 gpm. Main drains only capable of 224 gpm. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Immediate suspension item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
One ladder missing endcaps. Corrected by operator.
Same ladder extends > 6 inches from the pool wall. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Missing cover for one of the floor returns. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Intent to suspend item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gates with diagonal support wire. .2528(a) Diagonal members on fence and/or gate shall not exceed 1.75 inches. - Intent to suspend item.
Fence < 48" in places. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Both underwater lights not tightly installed. Corrected by operator. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(e) Provide a spare basket for pump. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Light not functioning in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
Pump room used for general storage. Items stored beside the equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms 141.8F. Maintain at 110F or less. |