Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameSYCAMORE AT TYVOLA
Address707 SYCAMORE CENTRE DR
 
City/State/ZIP
CHARLOTTE NC 28217
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 9/15/2022
Final Score @ Grade
28
General CommentsSend verification of night lighting to Marie Daley at 704-507-6806.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No pH 8.2 at time of inspection. .2535(1) Maintain pH at 7.2 to 7.8. Operator corrected to 7.4.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No One broken weir. .2518(k) Replace missing or broken weirs. Operator repaired and corrected
12 4 Pool maintenance: inlets and other fittings in place and in good repair No No No Light ring cover not in place and broken at time of inspection .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Operator repaired and corrected.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No Rope tangled at time of inspection. .2530(a) Lifesaving equipment should be conveniently located. Operator untangled and corrected.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter not working at time of inspection. .2518(g) Keep flow meter operational. Operator adjusted and corrected.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Some chemical in tubs in pump room. Items around piping and equipment in pump room. No 3' clearance. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Glass soap dispensers in restroom. No toilet paper in women’s stall. .2526(j) Provide soap and soap dispenser, no glass, at each sink. .2526(l) Provide toilet paper and dispensers in restrooms.