Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameSYCAMORE AT TYVOLA
Address707 SYCAMORE CENTRE DR
 
City/State/ZIP
CHARLOTTE NC 28217
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 2/2/2021
Final Score @ Grade
28
General CommentsITS for fence gap greater than 4", gates self-latching, records and flow meter. Changed to "W" Status. No signature due to COVID. Inspection with Chris Foggie, Derrick Morris and Ozzie Gonzalez Report to cfoggie@sycamoreattyvola.com Pool lights observed working, outer lights are on timer and unable to verify compliance for night swimming. Operator will send picture verification of lighting at night to go with Night Swimming form filled out with onsite visit from 2020. Pool not heated.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No pH 8.0 at time of inspection. .2535(1) Maintain pH at 7.2 to 7.8. Operator corrected to 7.3
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Records not including daily main drain checks and maintenance. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. *30 Day Intent to Suspend (ITS) item
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Debris in skimmer baskets at time of inspection. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator cleaned and corrected.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Side gate propped open, not latching every time closed at time of inspection. Gap in fencing posts greater than 4". Pool built 2018. .2528(a) Provide no openings in fence and/or gate greater than 4"x4". .2537(b) All gates and doors shall be self-closing, self-latching. *30 Day Intent to Suspend item
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter not working at time of inspection. .2518(g) Keep flow meter operational. Operator adjusted, it worked then stopped again. *30 Day Intent to Suspend item
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Some chemical in tubs in pump room. Items around piping and equipment in pump room. No 3' clearance. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
28 2 Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted No No No Showers off due to cold weather at time of inspection. .2526(h) Shower(s) shall be provided.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water over 110 degrees F in restrooms. .2526(i) Water in restrooms shall not exceed 110 F.