2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine at 0.6 ppm. Maintain chlorine through chlorinator at least 1.0 ppm. Immediate Suspension issued. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Pool pH at 7.0. Maintain pool pH at 7.2 to 7.8. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No main drain checks for month of July. Maintain daily record keeping for main drain checks.
CPO on vacation week of 7/21. For pool to be reopened, pool CPO must be present for daily visits. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some algae on pool walls and around ladders. Keep walls clean. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Water level low. Multi-port damaged and backwash could not be turned off. Bring water level up so skimmers operate per NSF standard. Required to reopen the pool. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Some build-up on waterline tile and depth markers. Keep clearly visible. Still visible at time of inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy rope degrading. Replace ring buoy with 33 ft. rope. Immediate Suspension issued. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Automated feeder could not be verified. Pump not operable due to damaged multiport. Pump was turned off. Feeder shall detect flow with loss of power from the pump. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Could not verify flow meter, pressure gauge, or equipment operable. Pump turned off at time of inspection due to damaged multiport. Repair multiport. Pump shall be operable to reopen the pool. Immediate Suspension issued for pump inoperable. |