4
|
6
|
Water quality: water temperature of heated pool |
No |
No
|
No |
Pool pH >8.2. Maintain at 7.2 to 7.8 through automated feeder. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No records for cyanuric acid or total alkalinity. Maintain weekly record keeping.
Some reagents expired. Replace expired reagents. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy grab rope degraded from environment. Replace with USCG approved ring buoy. If replacing rope, provide 33 ft. rope. Immediate Suspension issued. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door at gym not self-closing, self-latching. Sticking. Door nearest restrooms also sticking. Repair doors to self-close, self-latch.
Note - limiters on windows not viewed at time of visit. Ensure all windows are limited at 4" or less. Could not access rooms. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Grate at deck drain sticking up. Repair to eliminate trip hazard. Outside of required deck space. Located nearest back entry by stairwell. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
New automated chlorinator/acid feeder installed. Does not detect flow. Automated controllers shall detect no flow when operating and shut off with no flow. |