2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
0 ppm chlorine at time of inspection.
.2535(4) Maintain chlorine at least 1.0 ppm through NSF approved chlorinator.
*Immediate suspension item |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records missing weekly cyanuric acid reading, daily main drain checks and not accurate at time of inspection. .2535(11) Provide weekly recordings for cyanuric acid and total alkalinity.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable.
*permit item |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Doors onto pool deck not latching at time of inspection.
.2528(a) Ground level doors shall be self-closing, self-latching or self-closing and child protected by audible alarm.
*permit item |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Wood decking breaking out, screws missing, causing offsets greater than 1/2ā and not in good repair.
.2537(2) Decks shall be kept in good repair.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
.2522(a) Provide 6 ft of clear walking space around the outdoor pool at all times.
*permit item
Note: if deck is renovated submit in-field plan review with specifications. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Lighting coming detached from wall. .2524(c) Lighting fixtures shall not present a hazard to the public.
*permit item |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Stair missing return inlet fitting. Pump not working. Unable to verify flow meter. .2518(i) Return inlets shall be replaced when damaged or missing.
.2518(g) Keep the flow meter operational. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals in pump room. Leak at pump. Water on floor. Original construction.
.2533(d) Pump room floor shall be kept dry and free of standing water.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |