5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records not available at time of inspection.
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records.
.2535(11) The pool operator must maintain records for at least six months.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*Permit item |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Debris on pool floor and main drains. .2537(14) Keep pool surface and pool floor free of debris. Operator cleared drains, will return to verify floor is cleaned.
*Permit item |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Debris in skimmers. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator cleaned and corrected. |
|
10
|
2
|
Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints |
No |
No
|
No |
Safety rope missing at breakpoint at time of inspection, floats more than 5 ft apart when replaced. .2523(e) Safety rope shall be marked with colored floats, 5 ft. apart or less.
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint.
*Permit item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Items around pump and equipment. No backflow prevention on hose. Ventilation not working in pump/chemical room. Chemicals stored in pump room. Pool built '85. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump and chemical storage room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(d) Pump room floor shall be kept dry and free of standing water.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No airgap on backwash line. Pool built ‘85.
.2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
No toilet paper in men’s restroom stall. Toilet soiled in women’s restroom.
.2526(l) Provide toilet paper and dispensers in restrooms.
.2526(m) Keep restrooms and fixtures clean and in good repair. |