| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine tablets observed in skimmer baskets. G.S. 130A-2(3) Chlorine added directly to swimming pool. Chlorination must occur through chlorinator. Eliminate direct hazard to public.
*Immediate Suspension item. Contact Marie Daley at 704-507-6806 when chlorinator is fixed and chlorine is being added through chlorinator, not directly to pool. Pool MUST REMAIN CLOSED with "Pool Closed" signs posted until suspension is lifted by Health Dept. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records are not being kept daily (observed a few days recorded/week). No weekly cyanuric acid or alkalinity recorded. .2535 (11) The pool operator shall inspect the pool at least daily and maintain written records.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*permit item |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Skimmer equalizer lines observed plugged on wall, but NOT in skimmer. One skimmer basket plugged in wrong line. These need to be plugged per State Recommendations (in skimmer and on wall) prior to issuance of 2021 permit. Permit will be DENIED if this is not corrected.** .2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
*permit item |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder loose and not secure at 6 FT end of pool. .2521 Install ladders per manufacturer instructions. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Deck and coping chipped greater than 1/2" in multiple places and at skimmer basket and loose, cracked coping around pool. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
.2537(3) There shall be no loose coping.
*permit item |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Chlorinator not working at time of inspection. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions.*permit item |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operating at time of inspection.
.2518(g) Keep flow meter operational.
*permit item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Items around pump and equipment. Leak at filter and water on floor of pump room. Ventilation not working in pump/chemical room. Chemicals stored in pump room. Pool built '85. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(d) Pump room floor shall be kept dry and free of standing water. .2533(e) Provide continuous forced ventilation or cross ventilation in pump and chemical storage room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash. Pool built '85. .2513(b) Filter backwash shall be discharged through an air gap. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
Unable to locate hose bib for restroom at time of inspection. Pool built '85. .2526(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose. |