2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine 0.8 ppm at time of inspection.
.2535(4) Maintain chlorine at least 1.0 ppm. Operator corrected to 1.5 ppm through chlorinator. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Feature pump observed CHII-NI-1.5 FE, not CFII-NI-1.5 FE. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Operator updated PDSC form and submitted. Approved. No suction hazard. Corrected. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
1 weir observed missing at time of inspection.
.2518(k) Replace missing weirs. Operator replaced and corrected. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
New signage does not have correct wording. .2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering.
.2530(c) All pool signage shall be visible upon entrance to the pool and permanently affixed.
*ITS item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
One tub of chemicals stored in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Some items within 3' of piping in pump room.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. |