Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No record keeping for total alkalinity. Maintain weekly record keeping for total alkalinity. Intent to Suspend issued. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Crack across pool floor in deeper end of pool. Continue to monitor. May require repair in the future if worsens. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Overflow gutter damaged at sun shelf. Crack in clean-out grate. Noticed cracking in other locations also. No need of repair yet but may require repair in future.
Damage around clean-out grate at zero entry to pool. Offset >1/2". Repair to eliminate offset. Intent to Suspend issued. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Work being completed around concrete wall on pool deck. No depth marker on perimeter wall. Once complete, provide 3 ft. depth marker on perimeter wall. Intent to Suspend issued. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Handles on gates <40". Original construction. If ever replaced, raise to at least 40" - 45" measured from ground to meet ADA and rule requirement for horizontal.
Middle double door not self-latching. Repeat item with issues with these doors. Repair to self-close, self-latch. Intent to Suspend issued. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator. Install per NSF requirement. Original construction. If ever replaced, install as required. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Valve 7 required locked in place due to permit restriction flow on the backwash line. Screw removed. Install screw to lock in place. Intent to Suspend issued. Max flow is 300 gpm per filter restriction. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
One stall without toilet paper in women's; one stall with damaged toilet paper dispenser in men's. Provide toilet paper and keep fixtures in good repair. |