Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameWINDSOR RUN - SWIMMING POOL
Address2030 WINDSOR RUN LANE
 
City/State/ZIP
MATTHEWS NC 28105
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 11/15/2018
Final Score @ Grade
14
General CommentsIntent to suspend issued. Call Chris Sells when repairs are complete at 704 576 8678. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. .2518(h) Provide approved pump in good repair.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Observed no records of total alkalinity taken weekly. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Observed exit door that goes toward chemical closet not self-closing self-latching. Observed gate in outdoor area not self-closing self-latching. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Observed VFD not locked, pump at full flow, TDH indicates a flow rate of 250gpm, which exceeds the design flow rate of 175gpm. Pool does not have enough return fittings for this design flow. .2518(h) Provide approved pump in good repair.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Observed hot water in men's shower at 115F. .2626(i) Water in restrooms shall not exceed 110 F.