Water quality: pool water pH |
No |
No
|
No |
PH 7.1. .2535(1) Maintain pH at 7.2 to 7.8. - Pre-permit item. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Pool recently replastered. Changed from 18x18 main drains to 9x9 main drains. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Will need to go through in-field plan review as well. - Pre-permit item. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
New ring buoy with 60 foot throw rope. .2530(a) Provide USCG approved ring buoy with attached 41 foot throw rope. - Corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Pre-2010 fence. Decorative rocks added around the fence < 48" high throughout. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier.
Magna-Latch < 54” high. .2528(a) Gate latches shall be 54" in height. - Corrected. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Pool recently replastered. Eyeball fitting installed on one of the vacuum lines. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. - Pre-permit item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |