3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
pH < 6.8. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No weekend checks. Rarely checked Total Alkalinity or Cyanuric Acid over the summer. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, and pool water maintenance. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Intent to suspend item. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Leaves on pool floor and on wall mounted main drains. .2537(14) Keep pool surface and pool floor free of debris. - Intent to suspend item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmer baskets full of leaves. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Intent to suspend item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Fence < 48" high in places. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier.
Gap > 4" under the fence. .2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone not readily visible due to large pillars. Temporary signage in place on last inspection has been removed. .2530(f) Provide signage with location of emergency phone if not visible from all areas inside pool enclosure. - Immediate suspension item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Vacuum cap not securely closed. Ensure cap is closed such that it is only openable with a tool after done vacuuming. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. Corrected. |