Water quality: pool water pH |
No |
No
|
No |
pH 6.9 .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.4. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable.
.2535(11) Provide weekly recordings for cyanuric acid and total alkalinity.
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records.
Observed gaps in the pool record log book where data is being missed. Ensure that the log book records is kept properly everyday the pool is open for swimming. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed ring buoy to have rope that was no longer attached. Rope was reattached and made to be the proper length for this pool. (45 feet). |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Deck chair too close to pool edge. .2522(a) Provide 6 ft of clear walking space around the pool at all times. - Corrected.
Offsets > 1/2 inches between deck and coping. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. The deck has sections that appear to be sinking. They are not greater than 1/2 inch yet, but they need to be corrected before they become worse. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2535(6) Automatic chlorine and bromine, and acid feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation.
The feeder system did not appear to be powered upon arrival. It was powered up during the inspection, but it was unclear if it had automatic shut off as it was not able to be clearly demonstrated during the inspection. Ensure the automatic feeder system is working properly, and determine how the automatic shut off can be tested during a no-flow state of the system while the feeder is still powered up. -Intent to Suspend Issued. Deadline is 10/30/2026. Failure to correct the issues by that date may result in the closure of the pool. Contact C. Elmore at 704-507-6814 when corrections are made. |