Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form on file does not match what is installed. Updated PDSC form filled out and approved while onsite.
Vacuum plugs in place do not meet requirements. Pool built after May 2010. Provide self-closing vacuum caps. Corrected by operator. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladders loose or missing endcaps. Maintain secure and in good condition. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Section of fence at top of retaining wall < 48" high. Corrected by operator.
Back gate not self-closing. Corrected by operator. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Incorrect phone number posted. Corrected by operator.
911 has correct address, Kings III has 9840 Long Creek Club Dr. Ensure that Kings III and 911 have correct address. Corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Light not working in pump room. Provide lighting. |