Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions. Observed cover on vacuum line not staying closed due to broken latching mechanism. CPO changed vacuum line cover. EHS observed new vacuum line cover close properly. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmer baskets full of debris. CPO dumped baskets during inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy rope at 31ft which exceeded the required length of 29ft. CPO cut rope to 29ft. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Maintain 2" or less under fence and/or gate (post-May 2010). Observed sections of fence with 7-9inch gap underneath fencing. Pool was built in 2015. CPO covered gaps with fencing. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(h) Provide approved pump in good repair. Observed pump for waterfall feature taken apart and not in use. According to CPO, they are not using the water fall feature due to a leak. WATER FEATURE MUST REMAIN OFF. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed minor water on pump room floor.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Observed chemicals being stored in pump room. Pool was constructed in 2015. |